61 62
Key number: 8-85
- This value allows us to set speed of the double pump station in manual operation.
- Manufacturer setting is 0 % and must be changed to 100% (see paragraph
‘How to change the values’).
Settings with the password
- Once you set the values under key numbers: 8-62 and 8-85, press right button
which brings you to values where you have to insert the password number 25
- That will bring you to a second group of values which must be adjusted as
follows:
Please note: I will describe only those which must be changed and full description of
the key numbers you can nd in the instruction manual
Key number: 8-01
- A minimum difference between temperatures on the panels and the cylinder to switch the
double pump station ON
- A manufacturer pre-set value : 15 K (can be changed)
Key number: 8-02
- A minimum difference between temperatures on the panels and the cylinder to switch the
double pump station OFF
- A manufacturer pre-set value : 5 K (can be changed)
Key number: 8-30
- A solar nominal panel performance.
- A solar nominal panel performance is based for the calculation of the actual panel
performance together with the ow setting (8-37). Dependent of the actual panel
performance the digital controller can modulate pump speed and controller ow which will
increase performance and efciency of the solar system.
- A manufacturer pre-set value is 8 kW. You must change this value to 6 kW for every RM
Solar system.
Key number: 8-35
- Minimum pump speed in auto mode.
- A manufacturer pre-set value is 50%. You must change this value to 100% for every RM
Solar system.
Key number: 8-37
- This value allows us to set the ow on the solar system (no electronic ow meter
is needed).
- The ow is 1 L/min per collector. For two panel system the value is 2 L/min.
- If you install more than three panels this value must be changed.
3 panels – 3 L/min
4 panels – 4 L/min
5 panels – 5 L/min
And so on